|
The laboratories conducting these tests were commissioned by various companies involved in the original formulation and manufacture of the Copper-Zinc filter media known as KDF. Each test describes the purpose and procedure used as well as the results. Please contact us for complete documentation on any of the tests shown here. Biological Research Solutions, Inc. Client: KDF Fluid Treatment, Inc.
II. Procedures:
III. Results and Discussion:
Biological Research Solutions, Inc. By: John W. Wireman, Ph.D. Dated: February 25, 1991 Table 1 1 - Test Microorganism: Enterobacter aerogenes
Table 2
No Enterobacter aerogenes survivors were detectable on Day 11 or 19 Biological Research Solutions, Inc. By: John W. Wireman, Ph.D. Dated: February 25, 1991 Terralab Engineers Analysis No: 15712 This is to certify that we have examined: and found: The attached Report of Test is an integral part of this Certificate. Terralab by NSF Standard 53 REPORT OF TEST Water filtration unit tested to the requirements of National Sanitation Foundation (NSF) Standard Number 53, Drinking Water Treatment Units, Health Effects CAVEAT Product Description 3. Materials 3.0 General: Materials which contact water shall be inert and not impart odor, color or taste to the effluent water. The materials and construction shall be appropriate for the use environment. Units intended for outdoor use shall not deteriorate because of sunlight. Complies. See construction materials section. 3.1 Temperature resistance. Units, for cold water use only small not deteriorate when exposed to 100 degree F water. Units for hot water use shall withstand 180 degree F water for continuous use or 165 degree F if for intermittent hot water use. Complies. The traits are not marked for restricted temperature use and were tested for mechanical properties at 180 degrees F. 3.2 Corrosion resistance: copper alloys, type 300 stainless, steels, Monel metal, and plastic materials (see 3.6) do not require a corrosion resistant coating. Complies. See materials of construction section. 3.6 Plastics: Thermoplastic and thermoset plastics wetted by the water shall comply with the require ments of the U.S. PF&DA and /or NSF Standard 14. Complies. See materials of construction section. 3.7 Joining materials shall meet the requirements of section 3. Complies. See materials of construction section. 3.9 Gaskets, O Rings, Shaft Seals and Packing Materials shall meet the requirements of section 3. Complies. See materials of construction section. 4. Design and Construction 4.0 General: The units shall be designed and constructed so that environmental influences such as vibration, shock, climactic conditions and the manufacturer's recommended cleaning procedures will not adversely affect them. , There shall be no burrs, sharp edges or other hazards which could cause injuries to users or mamienance personnel, Complies. 4.0.1 Performance indication: The unit shall be provided with an effective alarm which will warn the user when the unit is no longer performing its design function. Acceptable warnings include: 4.0.1.3 Providing an obvious indication of the function's discontinuance, such as sharp reduction in flow or volumetric indication; or 4.4 Dispensing outlet: Faucets, spouts or outlets integral with the unit (except drinking outlets, see 4.5) shall be designed such that when the unit is installed as directed by the manufacturer the outlet will be directed downward and shall be a minimum of 1 inch above the flood level of the receptacle or sink. Complies. The unit is provided with an industry standard diverter valve which is used to replace the aerator on the end of the tap spout. In normal installations, the diverter valve, although it extends approximately 3/8 inch further than the replaced aerator, should not decrease the distance to the high flood level below 1 ". In the case of spouts which do not have an aerator, and are not threaded, the diverter valve cannot be used. Responsibility for compliance with the applicable plumbing code is the responsibility of the installer. Primary Drinking Water Regulations, or a similar standard established by any U.S. Federal regulatory agency for materials not included In the U.S. EPA regulations. No single sample shall exceed the MCL by more than the established analytical error for the method used. 5.2 Chemical Units: Chemical reduction shall be substantiated by tests showing compliance with the minimum requirements specified as follows: 5.2.1 Chemical reduction: Shall reduce the specified contaminants as shown in Table 1. Complies. See Table 1 Note: Since it was known that the sample material has little, if any, effect on organic materials, the test was continued using the challenge water until any one of the metallic inorganic elemental components reached the maximum allowable effluent concentration. Table 1
*No copper or zinc were added to the challenge water; no present acceptable levels are set for these elements, however it is anticipated that standards will be established.
5.1.2 Chemical: The arithmetic average of the active agent of each test unit shall not exceed the MCL of the U.S. EPA Primary Drinking Water Regulations, or a similar standard established by any U.S. federal regulatory agency for materials not included in the U.S. EPA regulations. No single sample shall exceed the MCL by more than the established analytical error for the method used. 5.2 Chemical Units: Chemical reduction shall be substantiated by tests showing compliance with the minimum requirements specified as follows: 5.2.1 Chemical Reduction: Shall reduce the specified contaminant/s as shown in Table 1. Complies. See Table 1. Note: The results given in this table are the readings at 100 percent of manufacturer's listed capacity. Table 1
*No copper or zinc were added to the challenge water; no present acceptable levels are set for these elements, however it is anticipated that standards will be established. 5.4 Working pressure and hydrostatic performance. 5.4.1.1 Complete assemblies shall withstand a hydrostatic pressure equal to 2.4 times the working pressure or 300 psig, whichever is greater, for 15 minutes without leakage of water from the unit. Complies. When pressurized to 300 psig at 180 degrees F, there was no failure or leakage of the end of 15 minutes at pressure. 5.4.1.5 Valves and controls subject to line pressure shall be water tight at 150 psig pressure after a minimum of 100,000 pressure cycles of 0 150 psig at 70 =/ 5 degrees F. 5.4.3 Disposable pressure vessels and all replaceable components subject to line pressure shall be constructed for a working pressure of at least 125 psig and shall meet the following requirements: 5.4.3.1 Withstand a hydrostatic pressure of 2.4 times the working pressure or 300 psig, whichever is greater, for 15 minutes without leakage. Complies. See paragraph 5.4.1.1 above. 5.4.4 Units designed for open discharge, including connecting tubing where required shall be con structed for a working pressure of at least 125 psig and the following requirement: 5.4.4.1 Complete assemblies, with the outlet plugged, shall withstand a hydrostatic pressure of 1.2 times the working pressure of 150 psig, whichever is greater, for 15 minutes without leakage. Complies. General Performance Burst test, non metallic pressure vessels Minimum design burst pressure is equal to 4 times the working pressure or 500 psig, whichever is the greater. Complies. Burst pressure: 933 psig 5.5 Filter media: All finer media which may be subject to plugging shall be supported to withstand for 15 minutes a pressure differential of 75 psig or a pressure differential equal to the maximum pressure drop the product design will permit when installed under a line pressure of 125 psig without breakdown which would permit the passage of untreated water or media into the effluent. Complies. Filter Media Test 5.6 Rated pressure drop: In line entire system units shall not have more than a 10 psig initial pres sure drop at the rated service flow. This does not apple if the unit has an integral flow control or orifice. These units shall meet the requirements of 5.7. 5.7 Rated service flow: 1 gpm 5.7.1 The rated service flow shall be as specified by the manufacturer. Complies. Measured flow 1.32 gpm 6 instruction and information 6.0 Operation, maintenance and installation instructions must comply with the requirements of this section. Complies. Installation instructions are provided; there are no user maintenance requirements. 6.1 The units must be labeled in compliance with the requirements of this section. 6.3 Purchase and sales information must comply with the requirements of this section. Complies. |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||